Gas air heating units Monzun
Gas units Monzun are determined for air heating, eventually for ventilating of rooms and industrial halls. In term of the gas device we speak about open or closed consumers with forced combustion air exhaust. Units are equipped with a complete regulation with automatics that secures safe operation. They are produced in an output line and in several modifications in accordance with the required function and purpose.
Supplied output line 15-93kW
With operating costs lowering is vera important the regulation. We offer three types of regulations for our units.
- 1-level regulation: Units VH,CV - E with the one-level output operate in mode set on set off.
- 2-level regulation: Units VH,CV - ED with the two-level output operate in mode max - min set off.
- 3-level regulation: Units VH,CV - EM with the fluently modulated output in range max - min set off.
Advantages of usage of modulated regulation
The heating system is designed on so-called calculating temperature. This temperature (generally -15, -12OC) are only a few days in a year. This implies, that most of the heating season is system overlarged. That leads to cycling of units increased load, property overheating increased consumption. The regulation fluently modulates the output of the unit so not to come to exceeding of adjusted temperature. Smooth operating without frequent setting on and setting off of units secures max. comfort in the staying zone with a lower consumption of gas which with increasing prices of gas markedly helps to lower costs on the property heating.
Monzun VH/CV
Version VH with an axial ventilator determined for local heating is produced in an output line from 15 kW to 81 kW
with an air flow 1300 to 7500 m3/h. Version CV with a radial ventilator determined for heating, is produced in an
output line from 15 kW to 93 kW with an air flows 1300 to 9000 m3/h. On this version is can be connected the
air-technical distribution.
Units VH/CV in two-level and moudlation version are provided with a regulator of ventilator revolutions that
secures the constant temperature of heated air.
Technical data Monzun VH/CV
Unit type |
Max. heating output |
Min. heating output |
Max. air flow at 20°C |
Min. air flow at 20°C |
Electric input of the unit |
Range* |
Increase of air temperature Δt |
Noise |
Weight |
VH 130 |
15,0 kW |
6,5 kW |
1300 m3/h |
550 m3/h |
200 W |
12 m |
33,0°C |
44 dB |
74 kg |
VH 180 |
22,0 kW |
10,4 kW |
1900 m3/h |
900 m3/h |
250 W |
15 m |
33,0°C |
46 dB |
90 kg |
VH 250 |
29,6 kW |
12,0 kW |
2750 m3/h |
1150 m3/h |
400 W |
17 m |
30,0°C |
48 dB |
92 kg |
VH 300 |
35,5 kW |
12,2 kW |
3000 m3/h |
1050 m3/h |
400 W |
18 m |
34,0°C |
49 dB |
93 kg |
VH 350 |
40,6 kW |
15,8 kW |
4000 m3/h |
1500 m3/h |
650 W |
23 m |
30,5°C |
54 dB |
93 kg |
VH 400 |
46,4 kW |
19,3 kW |
4600 m3/h |
1900 m3/h |
650 W |
25 m |
30,0°C |
58 dB |
130 kg |
VH 450 |
52,2 kW |
21,3 kW |
4600 m3/h |
1900 m3/h |
650 W |
25 m |
34,0°C |
58 dB |
130 kg |
VH 520 |
60,9 kW |
26,2 kW |
4600 m3/h |
1900 m3/h |
650 W |
25 m |
40,0°C |
58 dB |
130 kg |
VH 600 |
69,6 kW |
28,1 kW |
7500 m3/h |
2950 m3/h |
1250 W |
26 m |
28,0°C |
68 dB |
182 kg |
VH 700 |
81,2 kW |
35,6 kW |
7500 m3/h |
3200 m3/h |
1250 W |
26 m |
32,4°C |
68 dB |
182 kg |
* IN FREE SPACE IS THE RESIBUAL VELOCITY 0,25 m s-1
Unit type
|
Max. heating output
|
Min. heating output
|
Max. air flow at 20°C
|
Min. air flow at 20°C
|
Electric input of the unit
|
Applicable pressure
|
Increase of air temperature Δt
|
Weight
|
CV 130
|
15,0 kW |
6,5 kW |
1370 m3/h |
600 m3/h |
450 W |
110 Pa |
31,0°C |
81 kg |
CV 180
|
22,0 kW |
10,4 kW |
1750 m3/h |
800 m3/h |
450 W |
120 Pa |
36,0°C |
97 kg |
CV 250
|
29,6 kW |
12,0 kW |
3200 m3/h |
1300 m3/h |
1150 W |
180 Pa |
26,5°C |
104 kg |
CV 300
|
35,5 kW |
12,2 kW |
3200 m3/h |
1100 m3/h |
1150 W |
180 Pa |
32,0°C |
105 kg |
CV 350
|
40,6 kW |
15,8 kW |
4000 m3/h |
1500 m3/h |
1600 W |
180 Pa |
30,5°C |
113 kg |
CV 400
|
46,4 kW |
19,3 kW |
4600 m3/h |
1900 m3/h |
1600 W |
160 Pa |
30,0°C |
150 kg |
CV 450
|
52,2 kW |
21,3 kW |
4600 m3/h |
1900 m3/h |
1600 W |
160 Pa |
34,0°C |
150 kg |
CV 520
|
60,9 kW |
26,2 kW |
4600 m3/h |
1900 m3/h |
1600 W |
160 Pa |
39,5°C |
150 kg |
CV 600
|
69,6 kW |
28,1 kW |
8000 m3/h |
3200 m3/h |
3200 W |
180 Pa |
26,0°C |
230 kg |
CV 700
|
81,2 kW |
35,6 kW |
8000 m3/h |
3400 m3/h |
3200 W |
180 Pa |
30,5°C |
230 kg |
CV 800
|
92,8 kW |
40,8 kW |
9000 m3/h |
3800 m3/h |
3700 W |
130 Pa |
31,0°C |
240 kg |
Examples of installation
Installation by hanging under the ceiling |
Installation on the wall |
 |
 |
Examples of the combustion air exhaust
Horizontal combustion air exhaust |
 |
Horizontal combustion air exhaust with a condensate vessel |
 |
Vertical combustion air exhaust |
 |
MONZUN VH/CV - RTI
Air-technical gas units Monzun VH/CV-RTI ate determined for ventilating and ecological heating of rooms and hall with heated air. Version VH-RTI with axial ventilator determined for ventilation, eventually for local heating, is producen in an output line from 15 kW to 81,2 kW with an air flow 1200 to 6000 m3/h. The mixing chamber at version VH is occupied by filtration cloth at class filtration G2. Version CV-RTI with radial ventilator determined for ventilation, eventually central heating is produced in an output line from 15 kW to 92,8 kW with an air flow 1300 to 8000 m3/h. To this version can be connected the air-technical dust and eventually the intake point of units can be occupied with filters. All units VH/CV-RTI are equipped with the regulator of revolutions which secures the constant temperature of air at the exit. Units are at the intake equipped with the mixing chamber stepped with regulation valves for adjusting of chosen outside and circulatory air ratio in range 0 to 100%.
 |
Monzun VHRTI .01 Z |
 |
Key:
- Unit Monzun VH/CV-RTI
- 1 Box of the unit
- Exhaust of the heated air:
- Z grill with tilting louvres
- P flange for connection of Duct
- 1.3 Ventilator:
- Mixing chamber
- Body of the mixing chamber
- Flange and regulation valve of the outside air supply
- Flange and regulation valve of the circulatory air supply
- Operating of regulation valves:
- R lever (manual operating)
- S servodrive Belimo AM 24 SR (with operating box s SGF 24 M)
- 2.5 Filtration cloth EU 2
- Frame
Unit type |
Max. heating output |
Min. heating output |
Max. air flow at 20°C |
Min. air flow at 20°C |
Electric voltage/ supply of the unit |
Increase of air temperature Δt |
Weight |
VH-RTI 130 |
15,0 kW |
6,5 kW |
1200 m3/h |
550 m3/h |
230 V/200 W |
37°C |
125 kg |
VH-RTI 180 |
22,0 kW |
10,4 kW |
1750 m3/h |
900 m3/h |
230 V/250 W |
37°C |
146 kg |
VH-RTI 250 |
29,6 kW |
12,0 kW |
2600 m3/h |
1300 m3/h |
230 V/400 W |
32°C |
153 kg |
VH-RTI 300 |
35,5 kW |
12,2 kW |
2850 m3/h |
1400 m3/h |
230 V/400 W |
36°C |
154 kg |
VH-RTI 350 |
40,6 kW |
15,8 kW |
3500 m3/h |
1750 m3/h |
230 V/650 W |
35°C |
154 kg |
VH-RTI 400 |
46,4 kW |
19,3 kW |
4300 m3/h |
2100 m3/h |
230 V/650 W |
32°C |
200 kg |
VH-RTI 450 |
52,2 kW |
21,3 kW |
4300 m3/h |
2100 m3/h |
230 V/650 W |
36°C |
200 kg |
VH-RTI 520 |
60,9 kW |
26,2 kW |
4300 m3/h |
2100 m3/h |
230 V/650 W |
42°C |
200 kg |
VH-RTI 600 |
69,6 kW |
28,1 kW |
6000 m3/h |
2500 m3/h |
230 V/1250 W |
34°C |
255 kg |
VH-RTI 700 |
81,2 kW |
35,6 kW |
6000 m3/h |
2500 m3/h |
230 V/1250 W |
40°C |
255 kg |
Unit type |
Max. heating output |
Min. hea-ting output |
Max. air flow at 20°C |
Min. air flow at 20°C |
Electric voltage/supply of the unit – version Z |
Electric voltage/supply of the unit – version P |
Applicable pressure version Z/P |
Increase of air temperature Δt |
weight of version Z/P |
CV-RTI 130 |
15,0 kW |
6,5 kW |
1300 m3/h |
600 m3/h |
230 V/450 W |
230 V/1150 W |
100 Pa/280 Pa |
34°C |
132 kg/142 kg |
CV-RTI 180 |
22,0 kW |
10,4 kW |
1750 m3/h |
900 m3/h |
230 V/450 W |
230 V/1150 W |
60 Pa/250 Pa |
37°C |
154 kg/160 kg |
CV-RTI 250 |
29,6 kW |
12,0 kW |
2750 m3/h |
1400 m3/h |
230 V/1150 W |
230 V/1600 W |
160 Pa/300 Pa |
31°C |
165 kg/173 kg |
CV-RTI 300 |
35,5 kW |
12,2 kW |
3000 m3/h |
1500 m3/h |
230 V/1150 W |
230 V/1600 W |
110 Pa/270 Pa |
34°C |
166 kg/174 kg |
CV-RTI 350 |
40,6 kW |
15,8 kW |
3500 m3/h |
1750 m3/h |
230 V/1600 W |
3x400 V/2200 W (1 |
170 Pa/300 Pa |
35°C |
175 kg/180 kg |
CV-RTI 400 |
46,4 kW |
19,3 kW |
4000 m3/h |
1900 m3/h |
230 V/1600 W |
3x400 V/2200 W (1 |
110 Pa/310 Pa |
35°C |
220 kg/225 kg |
CV-RTI 450 |
52,2 kW |
21,3 kW |
4300 m3/h |
2100 m3/h |
230 V/1600 W |
3x400 V/2200 W (1 |
90 Pa/260 Pa |
36°C |
220 kg/225 kg |
CV-RTI 520 |
60,9 kW |
26,2 kW |
4500 m3/h |
2300 m3/h |
230 V/1600 W |
3x400 V/2200 W (1 |
60 Pa/230 Pa |
40°C |
220 kg/225 kg |
CV-RTI 600 |
69,6 kW |
28,1 kW |
6000 m3/h |
3000 m3/h |
230 V/3200 W |
3x400 V/4400 W (1 |
210 Pa/340 Pa |
35°C |
325 kg/335 kg |
CV-RTI 700 |
81,2 kW |
35,6 kW |
7000 m3/h |
3700 m3/h |
230 V/3200 W |
3x400 V/4400 W (1 |
110 Pa/280 Pa |
35°C |
325 kg/335 kg |
CV-RTI 800 |
92,8 kW |
40,8 kW |
8000 m3/h |
4200 m3/h |
3x400 V/4400 W (1 |
3x400 V/4400 W (1 |
220 Pa/220 Pa |
35°C |
335 kg/335 kg |
Euroklim and equipment
Gas heaters Monzun CV-Euroklim are determined into the air-technical setups and airconditioning units as a heating unit for air heating. They are supplied in aan output line from 15 kW to 93 kW in version with modulated output in range of minimal and maximal value. This device is not equipped with its own air ventilator.
To the unit is possible to supply this equipment:
- Bypass
- Mixing ventilator chamber
- Filters
Heater type |
Max. heating output |
Min. heating output |
Min. air flow at 20°C |
Explicit air flow at 20°C |
Max. air flow at 20°C |
Pressure loss [Pa] WITH AIR FLOW min. / exp. / max. |
Increase of air temperature Δt [°C] min. / exp. / max. |
Weight |
CV-Euroklim 130 |
15,0 kW |
6,5 kW |
1200 m3/h |
1300 m3/h |
1750 m3/h |
13/16/28 |
37/34/26 |
69 kg |
CV-Euroklim 180 |
22,0 kW |
10,4 kW |
1650 m3/h |
1900 m3/h |
2450 m3/h |
13/18/30 |
40/35/27 |
81 kg |
CV-Euroklim 250 |
29,6 kW |
12,0 kW |
2350 m3/h |
2750 m3/h |
3250 m3/h |
27/38/53 |
36/31/26 |
81 kg |
CV-Euroklim 300 |
35,5 kW |
12,2 kW |
2850 m3/h |
3000 m3/h |
4100 m3/h |
40/45/84 |
35/34/25 |
82 kg |
CV-Euroklim 350 |
40,6 kW |
15,8 kW |
3450 m3/h |
4000 m3/h |
4650 m3/h |
60/80/108 |
35/30/26 |
82 kg |
CV-Euroklim 400 |
46,4 kW |
19,3 kW |
3450 m3/h |
4600 m3/h |
5550 m3/h |
37/65/95 |
40/30/25 |
120 kg |
CV-Euroklim 450 |
52,2 kW |
21,3 kW |
3900 m3/h |
4600 m3/h |
6250 m3/h |
47/65/120 |
40/34/25 |
120 kg |
CV-Euroklim 520 |
60,9 kW |
26,2 kW |
4500 m3/h |
4600 m3/h |
7900 m3/h |
62/65/193 |
40/39/23 |
120 kg |
CV-Euroklim 600 |
69,6 kW |
28,1 kW |
5200 m3/h |
7500 m3/h |
9000 m3/h |
42/87/126 |
40/28/23 |
168 kg |
CV-Euroklim 700 |
81,2 kW |
35,6 kW |
6000 m3/h |
7500 m3/h |
10100 m3/h |
57/87/158 |
40/32/24 |
168 kg |
CV-Euroklim 800 |
92,8 kW |
40,8 kW |
8150 m3/h |
9200 m3/h |
11100 m3/h |
102/130/190 |
34/30/25 |
168 kg |
 |
- Monzun CV-Euroklim
- bypass
- mixing ventilator chamber
- regulation valve
- filter
- damping fitting piece
|
Setup RTF - I
 |
Key:
- Mixing ventilating chamber
- Gas heater
- Regulation valve with a servodrive (from above, from below, eventually front side)
- Filter EU3 (from above, from below, eventually front side)
- Elastic sleeve
- Dividing (valve) chamber with a servodrive
- Bypass
- Divider
- Bypass
- Divider (mixing chamber with side outlets and diffusers)
- Combustion air exhaust
- Air supply for combustion
- Gas connection
- Feeding connector, operating, warning lights
|
Setup type |
Type of heater Monzun |
Max. heating output |
Min. heating output |
Air flow at 20°C |
Engine electric supply [kW] |
Applicable pressure [Pa]* |
Increase of air temperature ∆t |
RTF-I 180 |
CV-Euroklim 180 |
22,0 kW |
10,4 kW |
2000 m3/h |
1,04 |
100 |
32,7°C |
RTF-I 250 |
CV-Euroklim 250 |
29,6 kW |
12,0 kW |
3200 m3/h |
2,05 |
100 |
26,4°C |
RTF-I 300 |
CV-Euroklim 300 |
35,5 kW |
12,2 kW |
4000 m3/h |
2,30 |
100 |
25,6°C |
RTF-I 350 |
CV-Euroklim 350 |
40,6 kW |
15,8 kW |
4600 m3/h |
3,90 |
80 |
26,2°C |
RTF-I 400 |
CV-Euroklim 400 |
46,4 kW |
19,3 kW |
5000 m3/h |
3,90 |
100 |
27,6°C |
RTF-I 450 |
CV-Euroklim 450 |
52,2 kW |
21,3 kW |
5500 m3/h |
3,90 |
100 |
28,2°C |
RTF-I 520 |
CV-Euroklim 520 |
60,9 kW |
26,2 kW |
6000 m3/h |
3,90 |
50 |
30,1°C |
RTF-I 600 |
CV-Euroklim 600 |
69,6 kW |
28,1 kW |
7000 m3/h |
5,50 |
80 |
29,5°C |
RTF-I 700 |
CV-Euroklim 700 |
81,2 kW |
35,6 kW |
8500 m3/h |
5,50 |
80 |
28,3°C |
RTF-I 800 |
CV-Euroklim 800 |
92,8 kW |
40,8 kW |
10000 m3/h |
9,00 |
50 |
27,5°C |
* APPLICABLE PRESSURE IS DETERMINED FOR COVERING OF EXTERNAL PRESSURE DROPS IN THE INTAKE.
Destratificator
-20 %
lowers costs
on heating |
- Not to come up to high temperature drop between upper and lower part of the space thereby non-effective heating, the destratificators are installed into the room that secure forced flow of heated air down.
- Destratificator is equipped with a thermoregulator that operates the ventilator run.
|
|
|
|
Type of destratificator
|
D1 |
D2 |
D3 |
Air flow at 20°C (m3/h)
|
4500 |
6500 |
9000 |
Ventilator revolutions (ot/min)
|
870 |
900 |
860 |
Acoustic pressure at 1,5 m dB(A)
|
48 |
52 |
56 |
Electri connection
|
230V/50Hz |
Engine coverage
|
IP 40 |
Weight (kg)
|
19,5 |
23 |
25,5 |
|
|
|
|
High of installation (m)
|
D1 |
D2 |
D3 |
Maximal
|
10 |
12 |
16 |