Home >  Air-condition elements >   KMM

                Add to Favorites

3D

KMM - Covering Grid

Dimensions in mm, weight in kg

1. Description

Cover grates (hereinafter grates) are used to cover side holes and free ends of piping, or to be fitted into the wall.

Grates prevent passing larger objects and are suitable for systems without dust, fibres, etc.

Square grates are fixed to side holes or free ends of piping with screws 6.3 x 16 according to ČSN 02 1232.25. Free ends of piping are adapted by notching in corners up to length of "C" and bending. Corners remain free. Notching, bending, cutting the side holes out, boring, and fitting the grate is made during assembly.

Grates together with frames are supplied as a unit.

Grates are designed for macroclimatic areas with mild climate according to ČSN EN 60721-3-0, for AA4 environment according to ČSN 33 2000-3, and BNV spaces acc. to ČSN 33 2320.

2. Design

Grates consist of a flange, panel made of tensile metal, and frame for fitting to wall if required. Dimensions A = 800 and higher have grates provided with a central stiffening belt.

  1. Design of grates as for the location is marked by a number next to the technical conditions designation.

    DESIGN
    LOCATION
    First supplementary number next to the technical conditions
    grates with flanges
    to sides of piping
    to free ends of piping
    .2
    grates with flanges, frame and holders
    for fitting to the wall
    .3

  2. Design of grates as for the surface painting and colour shades is marked by a number on the second place next to the technical conditions designation.

    DESIGN
    Second supplementary number
    Surface treatment by painting
    - ground coat
    .x0
    - RAL 9010 shade - white
    .x1
    - RAL 9001 shade - cream
    .x2
    - RAL 9006 shade - aluminium
    .x3
    Atypical shade
    - agreement with the manufacturer
    .x9

Installation examples

a) Square grates

Side of piping
Free end of piping
With frame for fitting to wall
c = 30
c1 = 15

b) Round grates

Free end of piping
With frame for fitting to wall
Size ø 100 - b = 25
up to ø 355 - b = 30
up to ø 560 - b = 40
up to ø 710 - b = 45
up to ø 900 - b = 50

 

3. Dimensions

 


ø D
d
n
b
Holders pcs
Weight of type
.2
.3
100
9,5
4
25
2
0,2
0,6
160
8
30
0,4
0,9
200
4
0,5
1,2
250
0,6
1,4
280
0,7
1,6
315
12
0,8
1,9
355
0,9
2,2
400
11,5
40
1,2
3,8
450
6
1,4
4,9
500
16
1,5
5,4
560
1,8
5,9
630
45
2,2
8,1
710
13,5
20
2,5
9,4
800
50
3,2
1,8
Connection dimensions of round grates correspond with ON 12 05 11.
 
AB
V1
m1
V2
m2
b
d
n
Holders pcs
Weight of type
.2
.3
125125
82,5
-
82,5
-
30
7
4
2
0,30
0,80
160125
100
-
82,5
-
0,35
0,90
160
100
0,40
1,00
200125
120
-
82,5
-
0,40
1,00
160
100
0,45
1,10
200
120
0,50
1,25
250125
50
190
82,5
-
6
0,45
1,15
160
100
0,50
1,25
200
120
0,60
1,30
250
50
200
8
0,65
1,55
315125
50
255
82,5
-
6
4
0,60
1,60
160
100
0,70
1,65
200
120
0,75
1,80
250
50
190
8
0,80
1,90
315
50
255
0,95
2,15
400160
100
240
100
-
6
0,80
1,90
200
120
0,90
2,10
250
50
190
8
0,95
2,15
315
80
255
1,10
2,45
400
100
240
1,30
2,80
500200
100
170
120
-
1,10
2,45
250
50
190
10
1,25
2,75
315
80
195
6
1,35
2,95
400
100
240
1,40
3,05
500
170
12
1,60
3,50
630250
100
235
50
190
10
4
1,35
2,85
315
80
165
1,45
3,10
400
100
240
6
1,65
3,50
500
170
12
1,80
4,00
630
235
2,30
4,50
800315
100
330
80
215
10
4
2,40
5,50
400
100
260
6
2,70
6,00
500
180
12
2,80
6,50
630
245
3,00
7,00
800
330
8
3,50
8,00
1000400
100
430
100
260
10
6
2,90
6,50
500
180
12
3,30
7,50
630
245
3,60
8,00
800
330
8
4,20
9,00
1250500
100
370
100
180
14
4,20
9,00
630
245
4,50
9,50
800
330
10
4,90

10,50

If required, we can supply all inter-dimensions of above given basic range.

4. Performace data

 

Coefficients of pressure losses

Up to size A = 630
on inlet side
ξ = 2,2
on outlet side
ξ = 1,5
From size A = 800
on outlet side
ξ = 2,4
on outlet side
ξ = 1,7
Loss of dynamic pressure is not included in values for outlet.

 

5. Data for ordering

Cover grate KMM 400 x 400 (ø400) - TPM 002/96 . 23 ……… pieces

 

Cover grate
KMM
400 x 400 (ø400)
-
TPM 002/96
.
2
3
 
Type
Size
Technical conditions
For side or free ends of piping
Paint - RAL 9006 shade - aluminium

 

6. Material, surface protection

The grate flanges and panels from tensile metal are made of material class 11 and coated as mentioned in article 2b.

Frames for fitting to the wall are provided only with a ground coat.

7. Packaging, transport, take - over, storage

Grates are supplied in cardboard packaging. While transported and stored they must be protected against mechanical damage and weather conditions.

If no method of take-over is mentioned in the order, handing the goods over to the carrier will be considered as a take-over.