RKKM - Circular Register

Dimensions in mm, weights in kg.
These specifications stipulate the production sizes and versions for "LEAKPROOF, CYLINDRICAL CONTROL DAMPERS RKKTM " (further only dampers). They are valid for production, design, ordering, delivery, assembly, operation and maintenance.

I. GENERAL INFORMATION

1. Description

1.1. The dampers consist of the body, the leaf and the control mechanism. They serve the regulation of the air flow in the piping by constricting the cross section.

1.2. The dampers are meant for environments protected against climatic influences of the category 3K5 according to ČSN EN 60 721-3-3 for BNV areas according to ČSN EN 1127-1 and AA4 environments according to ČSN 33 2000-3. The air flowing through the dampers must not contain solid, fibrous, adhesive or aggressive particles, and its temperature must lie in the range of -10 to + 60° C.

1.3. The maximum pressure difference and the speed of the air flow in the leakproof control dampers.

Size Max. pressure differenceMaximum speed of air flow ∆p [ Pa ] wmax [m.s-1]

TABLE NO. 1

Size
Max. pressure difference Δp [ Pa ]
Maximum speed of air flow wmax [m.s-1]
80
2000
18
100
2000
18
110
2000
18
125
2000
18
140
2000
18
150 *
2000
18
160
2000
18
180
2000
18
200
2000
18
225
2000
18
250
2000
15
280
2000
15
300
2000
15
310 *
2000
15
315
2000
15
355
2000
15
400
1500
12
450
1500
12
500
1500
12
560
1200
12
630
1200
12
* this version manufactured only on spiro piping

2. VERSIONS

The dampers can be delivered in these versions:

2.1. According to the control means

  • with manual control
  • for running of actuating mechanism
  • with control by two-positional actuating mechanism (230V, 24V)
  • without signaling the position
  • with control by two-positional actuating mechanism (230V, 24V)
  • with signaling the position
  • with control by actuating mechanism (24V SR) with continuous regulation of the position

2.1.1. Damper versions are designated according to the manner of control by a double-digit number behind the TP number.

TABLE NO. 2

Damper version - type of control
Double-digit number behind the TP number
Manual
. 01
For running of actuating mechanism
. 09
Actuating mechanism - regulation of position 230V
. 45
Actuating mechanism - regulation of position 230V + signalling of position
. 46
Actuating mechanism - regulation of position 24V
. 55
Actuating mechanism - regulation of position 24V + signalling of position
. 56
Actuating mechanism - continuous regulation 24V SR
. 57

2.2. According to manner of attachment

  • on cylindrical piping with flanges according to ON 120517
  • on spiro piping
  • on spiro piping with edge sealing

2.3. Designation example for ordering:

LEAKPROOF, CYLINDRICAL CONTROL DAMPER RKKT - 100 - P TPM 030/03 .56

LEAKPROOF, CYLINDRICAL CONTROL DAMPER
RKKT
-
100
-
P
TPM 030/03
.56
  Type   Size   Version for attachment:
P - on cylindrical piping with flanges according to ON 120517
S - on spiro piping
SL - on spiro piping with edge sealing
Specifications

Versions (according to point 2.1.1)

It is necessary to talk with the manufacturer beforehand regarding orders for versions with a different type of actuating mechanism.

 

3. Positioning, assembly

3.1. The dampers are meant for installation in air piping. The operating position is whatever you like.

3.2. The minimum space for the control mechanism is 250 mm.

3.3. When positioning the dampers in piping, it is necessary to respect the value "a" (overlap of open leaf). The value "a" is listed in tables No. 3 and 4.

4. Dimensions, nomenclature, weights

4.1. Dimension column, dimensions (mm), through-flow (effective) area (m2), weights (kg) 4.1.1 Damper for connecting to cylindrical piping with flanges according to ON 120517

TABLE NO. 3

Size
Dimensions
Openings
Effective area Sef
Weight
øD
L
a
ød
80
150
110
4
0,0047
0,94
100
150
130
4
0,0074
1,12
110
150
140
4
0,0090
1,21
125
150
155
8
0,0117
1,37
140
150
170
8
0,0147
1,51
160
150
195
8
0,0194
1,83
180
150
10
215
8
0,0246
2,15
200
150
20
235
8
0,0305
2,43
225
150
32,5
260
8
0,0387
2,76
250
150
45
285
8
0,0479
3,11
280
150
60
315
8
0,0603
3,52
300
150
70
335
12
0,0693
3,85
315
150
77,5
350
12
0,0765
4,10
355
150
97,5
390
12
0,0973
4,75
400
200
95
445
12
0,1238
6,75
450
200
120
495
12
0,1569
7,80
500
200
145
545
16
0,1940
9,00
560
200
175
605
16
0,2437
10,40
630
200
210
680
16
0,3088
12,80

4.1.2 Damper for connecting to spiro

TABLE NO. 4

Size
Dimensions
Effective area Sef
Weight
øD
øD1
L1
a
80
79
240
0,0047
0,85
100
99
240
0,0074
1,00
110
109
240
0,0090
1,10
125
124
240
0,0117
1,20
140
139
240
0,0147
1,35
150
149
240
0,0170
1,45
160
159
300
0,0194
1,80
180
179
300
0,0246
2,05
200
199
300
0,0305
2,30
225
224
300
0,0387
2,60
250
249
300
0,0479
2,90
280
279
300
0,0603
4,20
300
299
350
0,0693
5,00
310
309
350
0,0740
5,25
315
314
350
0,0765
5,35
355
354
350
0,0973
6,20
400
399
450
0,1238
8,60
450
449
450
0,1569
9,90
500
499
450
25
0,1940
11,30
560
559
450
55
0,2437
13,00
630
629
450
90
0,3088
15,20

Effective area for completely open damper Sef [m2 ].

Open leaf overlaps the body of the damper on both sides by the value of "a".

The weights listed are valid for control dampers with manual control and for dampers for running an actuating mechanism.

On control dampers controlled by an actuating mechanism, it is necessary to add its weight - see table No. 5.

4.2. Structural design

4.2.1 Damper for connecting to cylindrical piping with flanges according to ON 120517

Damper with manual control mechanism
Damper with control by actuating

4.2.2 Damper for connecting to spiro

Damper with manual control mechanism
Damper with control by actuating
  Position:
  1 - body of control damper
  2 - sealing leaf of damper
  3 - control lever
Dampers for running of actuating mechanism: they are furnished with a neck journal having a diameter of 16 mm and a length of 50 mm.

 

II. TECHNICAL DATA

5. Electrical components, connection diagram

5.1. Types and weights of the actuating mechanisms for control of the dampers:

TABLE NO. 5

Uses for the dampers
Type of actuating mechanism
Signalling of position
Torque moment
Weights of actuating mechanism
Dimensions L x H x W
Dampers up to a size of 315 mm
Belimo LM 230 - S
YES
4 Nm
0,65 kg
116x70x66
Belimo LM 230
NO
0,65 kg
Belimo LM 24 - S
YES
0,65 kg
Belimo LM 24
NO
0,65 kg
Belimo LM 24 SR
YES
0,62 kg
Dampers of size 355 mm to 500 mm
Belimo NM 230 + SN1
YES
8 Nm
0,93 kg
140x70x81
Belimo NM 230
NO
0,80 kg
Belimo NM 24 + SN1
YES
0,93 kg
Belimo NM 24
NO
0,80 kg
Belimo NM 24 - SR
YES
0,90 kg
Dampers of size 560 mm to 630 mm
Belimo AM 230 - S
YES
18 Nm
1,30 kg
191x78x92
Belimo AM 230
NO
1,30 kg
Belimo AM 24 - S
YES
1,30 kg
Belimo AM 24
NO
1,30 kg
Belimo AM 24 - SR
YES
1,30 kg
* Accessories: SN1 - auxiliary change-over contact for the actuating mechanism of the NM group (it is a delivery component)

5.2. Connection diagram for actuating mechanisms LM 230 - S and LM 230

with signaling of position
without signaling of position

5.3. Connection diagram for actuating mechanisms LM 24 - S and LM 24

with signaling of position
without signaling of position

5.4. Connection diagram for actuating mechanism NM 24 SR

with continuous control of position

5.5. Connection diagram for actuating mechanisms NM 230 and NM 230 + SN1

NM 230 - without signaling of position
auxiliary switching contact SN 1 for signaling of position

5.6. Connection diagram for actuating mechanisms NM 24 and NM 24 + SN1

NM 24 - without signaling of position
auxiliary switching contact SN 1 for signaling of position

5.7. Connection diagram for actuating mechanism NM 24 SR

with continuous control of position

5.8. Connection diagram for actuating mechanism AM 230 - S, AM 230

with signaling of position
without signaling of position

5.9. Connection diagram for actuating mechanism AM 24 - S, AM 24

with signaling of position
without signaling of position

5.10. Connection diagram for actuating mechanism AM 24 - SR

with continuous control of position

 

6. Pressure losses

 

Pressure losses dependent on the turning of the damper's leaf
  V [m3.h-1] - through-flow volume of air
  ∆p [Pa] - pressure loss when ρ =1,2 kg.m-3
  w [m.s-1] - flow speed
  α [ ° ] - angle of leaf's turning

 

7. Material, surface treatment

The body of the damper and the leaf are made of galvanized sheet; the leaf's journals are of steel. The version on spiro piping can come with or without a rubber edge seal. The damper is delivered without further surface treatment.

III. CHECKING, TESTING

8.1. The dimensions are checked by means of the usual measuring instruments according to the norm for non-tolerable dimensions used in air technology.

8.2. Intermediate operation checks of the parts and main dimensions are carried out according to the drawing documents.

8.3. After the plant assembly, a check of the functioning of the closing mechanism and the electrical components is carried out.

IV. PACKING, TRANSPORT, TAKING OVER, STORAGE

9. The dampers are shipped in bulk by covered means of transport. In agreement with the customer, it is possible to ship the dampers on pallets.The dampers must be protected against mechanical damage when handling during the time of transport and storage.

Should packaging material be used, it is non-returnable and its price is not included in the price of the damper.The manufacturer will charge a fee for the packaging material in agreement with the requirements of law 477/2001 Sb.

10. If the manner of take-over is not stated in the order, the handing over of the dampers by the transporters will be considered as the take-over.

11. The dampers must be stored in covered warehouses, in areas without aggressive vapors, gases and dust. In the warehouses, a temperature within the range of -5 to +40° C and a relative humidity of max. 80 % must be maintained.

12. The manufacturer grants a warrantee for the dampers of 24 months from the date of shipment.

13. Within the delivery capacity, there is the complete damper in the version ordered.

V. ASSEMBLY, SERVICE, MAINTENANCE, REVISION

14. The assembly consists of installing the damper in the air distribution system and if required, connecting the actuating mechanism to the electric net. Connection of the actuating mechanism to the electric net can only be done by someone who knows the full wording of notifications ČÚBP and ČBÚ 50/1978 Sb.

VI. RELEVANT NORMS, NOTIFICATIONS AND PROTOCCOLS

ČSN 33 2000-3 : 1995. . . . . . . . .Electrical regulations. Stipulation of the basic characteristics
ČSN 33 2000-4-41 : 2000. . . . . .Protection against injury by electric current
ČSN 33 2000-4-47 : 1997. . . . . .Measures to ensure protection against injury by electric current
ČSN 33 2000-5-54 : 1996. . . . . .Grounding and electric conductors
ČSN 33 2000-6-61 : 1994. . . . . .Procedures for initial revision
ČSN 33 2030 : 2002. . . . . . . . . . .Protection against the dangerous effects of static energy
ČSN EN 1127-1:1998. . . . . . . . . .Explosive environment. Limitation and protection against explosion
ČSN EN 60 721-3-3 : 1997. . . . . Classification of the environmental conditions
Notice ČÚBP Nr. 48/82 Sb.. . . . .Basic requirements for ensuring work safety and the safety of the technical equipment
Notice ČÚBP Nr. 324/90 Sb. . . . Work safety and the safety of the technical equipment during construction work
Notice ČBÚ Nr. 50/78 Sb.. . . . . . Expertise in electrical engineering