VAPM - Turbulent Air Outflow Anemostat (fixed fins)

Dimension in mm, weights in kg.

These technical conditions define the range of produced dimensions and versions of "Vortical anemostats of small diameter with fixed ribs"("terminal units") VAPM 125, 160, 200, 250, 315, 400. These technical conditions apply to the manufacture, design, ordering, assembly, operation and maintenance.

I. GENERAL

1. Description

Air terminal units with fixed ribs are the end point of an air conditioning system, which distributes the air led into the room for ventilation or cooling. Vortical output of air ensures intensive mixing with the existing air. This greatly reduces the temperature and speed of the airflow. Depending on the required volumetric airflow, location and noise suppression, the terminal units are delivered with or without diffusers.

Air terminal units are suitable for small rooms (ca 2.6 to 4 m) and for up to 30 air exchanges per hour. VAPM 125 to 400 terminal units supplement the existing line of vortical air terminal units with fixed ribs VVPM 300 to 625.

2. Versions

Depending on customer's requirement, air terminal units are delivered with rectangular or circular front plate - diffuser. Front plates include radial fixed ribs. The air duct can be connected through the connection box from the side or from the top, using circular necks. Connection boxes with connection from the side can be delivered with or without a regulation flap; connection boxes with connection from the top do not have regulation flaps:

Air terminal units are destined for environments protected from the elements, grade 3K5 according to ČSN EN 60 721-3-3 and for explosion-hazard free rooms according to ČSN EN 1127-1

VAPM/K version Circular front plate
VAPM/C version Rectangular front plate

3. Dimensions

 

Horizontal connection

Dimension
∅C
∅CD
øK
øKD
øD
øB
∅A
A1
A¨2
H1
H3
H5
E
F
125
198
198
198
200
98
128
297
260
260
220
250
150
130
62
160
248
248
248
250
123
163
320
320
320
240
270
175
160
75
200
298
298
298
300
158
203
390
370
350
275
305
210
175
95
250
298
348
298
350
198
253
455
440
420
335
373
250
195
115
315
398
398
398
450
248
318
500
560
540
380
418
300
255
150
400
498
498
498
570
313
403
600
700
680
430
468
365
325
182

VAPM .../C/V

VAPM .../C/D/V

VAPM .../K/V

VAPM .../K/D/V

 

Vertical connection

Dimension
øE
∅C
∅CD
øK
øKD
øD
øB
H
HD
H2
H4
H6
H7
125
123
198
198
198
200
98
128
50
80
100
175
130
205
160
158
248
248
248
250
123
163
50
80
110
185
140
215
200
198
298
298
298
300
158
203
50
80
115
190
145
220
250
248
298
348
298
350
198
253
50
90
120
195
165
240
315
313
398
398
398
460
248
318
50
90
135
227
185
277
400
398
498
498
498
570
313
403
50
90
158
248
220
310

VAPM .../C

VAPM .../C/D

VAPM .../K

VAPM .../K/D

VAPM .../C/S

VAPM .../C/D/S

VAPM .../K/S

VAPM .../K/D/S

4. Weight

 

Dimension
Connection
Separate front plate
Horizontal
Vertical
125
2,5
0,7
0,65
160
3,5
1,0
0,89
200
4,5
1,5
1,16
250
6,0
2,0
1,68
315
7,5
3,0
2,5
400
11,0
4,5
3,9

 

5. Location, assembly

Air terminal units of all dimensions are suitable for installation into the ceiling or outside enclosed ceilings. Front plate or front plate with diffuser are attached to the connection box using a central bolt and a bracket. Connection boxes are fitted with suspension brackets.

Examples of suspension follow

Installation into the ceiling
Installation outside enclosed ceiling

 

Method of suspension

Front plate flushed into intermediate ceiling
Front plate located above a grille
Air terminal unit installed into intermediate ceiling with diffuser
Air terminal unit installed without intermediate ceiling with diffuser

 

II. TECHNICAL SPECIFICATION

 

Airflow depending on the version

without diffuser VAPM / C VAPM / K
with diffuser VAPM / C / D VAPM / K / D

 

Dimension
125
160
200
250
315
400
V max [m3.h-1]
100
150
250
300
650
900
V min [m3.h-1]
35
55
90
105
230
280
LWA max [dB(A)]
36
36
37
33
44
39
LWA min [dB(A)]
< 20
< 20
< 20
< 20
< 20
< 20
Sef [m2]
0,0049
0,0089
0,0141
0,0167
0,0365
0,0440

 

6. Calculation and decisive values

 

V [m3.h-1] - volumetric airflow per one terminal unit
∆pc [Pa] - total pressure drop at ρ = 1,2 kg.m-3
LWA [dB(A)] - acoustic power level
A, B [m] - distance between two terminal units
X [m] - horizontal distance from center of the terminal unit to the wall
H [m] - distance from the terminal unit to floor - from 2,6 to 4,0 m
H1 [m] - distance between the ceiling and the occupied zone
L [m] - horizontal + vertical distance (X+H1)
wH1 [m.s-1] - medium speed of airflow between two air terminal units at the distance H1
wL [m.s-1] - medium speed of airflow at the wall surface
wef [m.s-1] - effective output speed of air at the air terminal unit
∆tP [K] - difference between the temperature of air led into the room and room temperature
∆tL [K] - difference between the temperature of air in the center of the airflow at distance L and room temperature: L = A/2 + H1 or L = B/2 + H1 or L = X + H1

Acoustic power levels and pressure drops

1. VAPM - horizontal connection, without diffuser
2. VAPM - horizontal connection, with diffuser
3. VAPM - vertical connection, without diffuser
4. VAPM - vertical connectioní, with diffuser

Correction coefficients to compensate for the angle of the regulation flap

Correction to diagram 1
Correction to diagram 2
Dimension (without diffuser)
Angle of regulation flap
0o
45o
90o
125
∆pc
×1,0
×1,2
×2,2
LWA
-
-
-
160
∆pc
×1,0
×1,4
×2,5
LWA
+3
-
-
200
∆pc
×1,0
×1,3
×1,9
LWA
+3
+4
+5
250
∆pc
×1,0
×1,4
×2,1
LWA
-
-
+1
315
∆pc
×1,0
×1,4
×2,1
LWA
-
-
+1
400
∆pc
×1,0
×1,4
×2,1
LWA
-
-
+2
Dimension (with diffuser)
Angle of regulation flap
0o
45o
90o
125
∆pc
×1,0
×1,3
×2,4
LWA
-
-
-
160
∆pc
×1,0
×1,4
×2,6
LWA
-
+1
+3
200
∆pc
×1,0
×1,4
×2,1
LWA
-
+1
+4
250
∆pc
×1,0
×1,4
×2,4
LWA
-
-
+1
315
∆pc
×1,0
×1,4
×2,5
LWA
-
-
+1
400
∆pc
×1,0
×1,4
×2,4
LWA
-
-
+2
5. VAPM Effective speed of airflow
6. VAPM Temperature coefficient
Volumetric airflow: V = 3600.wef.Sef [m3h-1]
7. VAPM 125 Speed of airflow - without diffuser
8. VAPM 125 Speed of airflow - with diffuser
9. VAPM 160 Speed of airflow - without diffuser
10. VAPM 160 Speed of airflow - with diffuser
11. VAPM 200 Speed of airflow - without diffuser
12. VAPM 200 Speed of airflow - with diffuser
13. VAPM 250 Speed of airflow - without diffuser
14. VAPM 250 Speed of airflow - without diffuser
15. VAPM 315 Speed of airflow - without diffuser
16. VAPM 315 Speed of airflow - with diffuser
17. VAPM 400 Speed of airflow - without diffuser
18. VAPM 400 Speed of airflow - with diffuser

Example

Input data:
air terminal unit V = 100 m3.h-1
∆tp = - 8 K
H1 = 1,1 m
A = 3,0 m
X = 1,5 m

Diagram 2:
∆pc = 17 Pa
LWA = 27 dB(A)

Diagram 6:
L (between terminal units) = A/2 + H1 = 2,6 m
∆tL /∆tp = 0,026
∆tL = - 8 . 0,026 = - 0,208 K
L (at the wall) = X + H1 = 2,6 m
∆tL /∆tp = 0,026
∆tL = - 8 . 0,026 = - 0,208 K

Diagram 10:
wH1 = 0,18 m.s-1 (between terminal units)
wL = 0,18 m.s-1 (at the wall)

III. SAMPLE DESIGNATION (USE WHEN ORDERING)

AIR TERMINAL UNIT VAPM 160 C / D / V / P / R - TPM 010/00

AIR TERMINAL UNIT
VAPM
160
C
/
D
/
V
/
P
/
R
-
TPM 010/00
  Type Dimensions C - rectangular front plate
K - circular front plate
  D - front plate with diffuser
no designation - front plate without diffuser
  V - horizontal connection
S - vertical connection
  P - air outlet from terminal unit into the room
O - air inlet from room into the terminal unit
  with regulation flap   technical conditions

 

IV. MATERIAL

All parts are made of zinc-plated steel sheet. The surface of the front plate and diffuser is coated with white baked varnish, RAL 9010 shade. Other RAL shades must be negotiated with the manufacturer in advance.
Connection boxes are made of zinc-plated steel sheet.

V. PACKING, TRANSPORT, INSPECTION, STORAGE

Air terminal units are transported in carton boxes as bulk cargo, using suitable covered means of transport. When agreed upon with the manufacturer, the terminal units can be loaded onto pallettes or wooden crates. Air terminal units must be protected from mechanical damage during transport and storage.

Unless the acceptance procedure is defined in the order, the disposition of the terminal units to the carrier will be considered the acceptance of the terminal units by the customer.

Air terminal units must be stored in closed rooms, out of the reach of aggressive vapours, gases and dust. Storage temperature must be -5 to +40 °C and relative humidity max. 80 %.

The manufacturer warrants the terminal units for 18 months since the start of operation; 24 months from the date of manufacture maximum.

VI. RELATED STANDARDS, REGULATIONS AND PROTOCOLS

ČSN 12 0000 . . . . . . . . . . . .Air conditioning equipment. Terms.
ČSN 33 2000-5-54 . . . . . . .Grounding and electrical cables.
ČSN 33 2000-6-61 . . . . . . .Procedure of initial revision.
ČSN 33 2030 . . . . . . . . . . . .Protection from the dangerous effects of static electricity.
ČSN EN 60721-3-3. . . . . . . Environmental conditions classification.
Vyhl. ČÚBP č. 48/82 Sb. . . Basic requirements of safety of work and of technical equipment.
Vyhl. ČÚBP č. 324/90 Sb. . Safety of work and of technical equipment during construction work.