Dimensions in mm, weights in kg.
These technical conditions define a series of the manufactured sizes and versions of the following large outlets (hereinafter outlets): VPVM - K 400, 600, 800, 1000, 1200, 1480, VPVM - S 400, 600, 800, 1000, 1200, 1500, 2000, VPVM - R 800, 1000, 1200, 1400, 1600, 2000 , heights of 750, 1000, 1250, 1500 and 2000 mm.
They apply to manufacturing, designing, ordering, deliveries, installation and operation.

I. GENERAL

1. Description

Large outlets are terminal air-conditioning elements for the distribution of air in air-conditioned and ventilated rooms. They are intended for the inlet of treated outdoor air directly into the living (working) area. In order to ensure stabilized air flow in the living area, the temperature of inlet air must be lower by 1 to 3°C then the temperature of air in the ventilated room. Outdoor air is let in with low velocity at the floor, to take harmful substances from the living area to ceiling.

2. Design

The following types of outlets are supplied: round outlets to be installed into a space, wall-mounted outlets with semi-circled ground plan, and corner outlets with quarter-circled ground plan. Piping is connected to outlets from above to round connecting socket. Outlets are supplied with or without control flaps.

Outlets are intended for installation in environments protected from weather conditions, class 3K5, according to ČSN EN 60 721-3-3 and in BNV rooms according to ČSN EN 1127-1.

3. Dimensions

 

Round outlet VPVM - K

Size
400
600
800
1000
1200
1480
øA
400 600 800 1000 1200 1480
øD
313 498 558 628 708 798
Height H: 750, 1000, 1250, 1500, 2000

Wall-mounted outlet VPVM - S

Size
400
600
800
1000
1200
1500
2000
A
400 600 800 1000 1200 1500 2000
B
330 490 550 620 700 850 1100
C
155 235 265 290 320 370 480
øD
248 398 448 498 558 628 798
Height H: 750, 1000, 1250, 1500, 2000

Corner outlet VPVM - R

Size
800
1000
1200
1400
1600
2000
A
400 500 600 700 800 1000
C
170 210 250 290 330 390
øD
248 313 398 448 448 498
Height H: 750, 1000, 1250, 1500, 2000

 

4. Weights

 

 
Size
Outlet height H [mm]
Regulation
750
1000
1250
1500
2000
VPVM − K
400
8,8
11,0
13,0
14,5
18,5
0,8
600
14,0
17,0
20,0
23,0
29,0
1,7
800
20,0
24,0
27,0
31,0
38,0
2,0
1000
27,0
31,0
35,5
40,0
48,5
2,5
1200
35,0
40,0
45,0
50,0
60,0
3,0
1480
46,5
53,0
59,0
65,0
77,0
3,7
VPVM − S
400
11,0
13,0
16,0
18,5
24,0
0,6
600
17,0
21,0
25,0
29,0
37,0
1,2
800
21,0
26,0
30,0
35,0
44,0
1,4
1000
25,5
31,0
36,0
41,5
52,0
1,6
1200
30,5
36,5
43,0
49,0
61,0
2,0
1500
37,0
47,0
54,5
62,0
76,5
2,5
2000
58,0
67,0
77,0
86,0
106,0
3,7
VPVM − R
800
12,0
15.0
17,5
20,5
26,5
0,6
1000
15,0
19,0
22,5
26,0
33,5
0,8
1200
19,0
23,5
28,0
32,0
41,0
1,2
1400
23,0
28,0
33,0
38,0
48,5
1,4
1600
26,5
32,0
38,0
43,5
55,0
1,4
2000
35,0
42,0
49,0
56,0
70,0
1,7

 

Note: The weights provided apply to outlets without control equipment. For versions including control equipment, the weight of the control equipment has to be added.

5. Location, Installation

Round outlets VPVM - K are intended for installation in free space, to be anchored to the floor. Wall-mounted outlets VPVM - S and corner outlets VPVM - R are installed onto walls and in corners, to be anchored either to the floor or to the wall (in the corner).

Floor-mounting example

VPVM - K
VPVM - S
VPVM - R
Anchoring example - detail X
Legend:
1. VPVM
2. anchoring plate
3. metal sheet screw ø 4,2 mm
4. countersunk screw ø 6 mm
5. dowel
Large outlet supply includes 6 anchoring plates (Pos. 2) and 6 metal-sheet screws, ø 4,2 mm (Pos. 3).
Connecting material (Pos. 4 and 5) is not included in the supply.

II. TECHNICAL DATA

Preliminary outlet design

Vmax [m3.h−1]
Size
socket øD [mm]
Outlet height H [mm]
750
1000
1250
1500
2000
VPVM − K
400
313
1250
1400
1500
1650
1800
600
498
2400
2600
2900
3100
3300
800
558
3100
3450
3600
3900
4200
1000
628
3800
4230
4500
4800
5300
1200
708
4700
5300
5500
6000
6500
1480
798
6100
6660
7000
7660
8100
VPVM − S
400
248
660
730
770
830
900
600
398
1400
1530
1700
1800
1900
800
448
1800
2000
2100
2250
2450
1000
498
2200
2430
2600
2800
3000
1200
558
2750
3050
3200
3450
3700
1500
628
3450
3800
4000
4300
4600
2000
798
5150
5800
6000
6500
7000
VPVM − R
800
248
660
730
770
830
900
1000
313
1150
1200
1400
1500
1600
1200
398
1400
1530
1700
1750
1900
1400
448
1600
1750
1800
2000
2150
1600
448
1800
2000
2100
2250
2450
2000
498
2200
2430
2600
2800
3000

 

Effective area Sef [m2]
VPVM − K
π . D . H . K
K = 0,63
VPVM − S
0,5. π . A . H . K
VPVM − R
0,5. π . A . H . K

 

6. Calculation and Determination Quantities

 

V [m3.h-1] - volumetric flow rate for one outlet
∆pc [Pa] - total pressure loss at ρ = 1,2 kg.m-3
LWA [dB(A)] - acoustic power level
wL [m.s-1] - flow velocity in L distance from outlet
∆tP [K] - difference between inlet air temperature and room air temperature
∆tL [K] - difference between room air temperature and flow air temperature in L distance

 

Pressure Losses and Acoustic Powers

 

Correction to outlet height (applicable to Diagrams 1 to 3)

 
Outlet height H
750
1000
1250
1500
2000
Δpc
x 1,1
x 1
x 0,9
x 0,8
x 0,7
LWA
+ 1
0
− 1
− 1
− 2
1. VPVM - K
2. VPVM - S
3. VPVM - R

 

Flow Velocity and Temperature Coefficient

 

Correction to outlet height (applicable to Diagrams 4 to 22)

 
Outlet height H [ mm ]
750
1000
1250
1500
2000
wL [m.s-1]
x 0,95
x 1
x 1,05
x 1,1
x 1,15
∆tL / ∆tP
x 0,65
x 0,7
x 0,75
x 0,8
x 0,9
4. VPVM - K 400
5. VPVM - K 600
6. VPVM - K 800
7. VPVM - K 1000
8. VPVM - K 1200
9. VPVM - K 1480
10. VPVM - S 400
11. VPVM - S 600
12. VPVM - S 800
13. VPVM - S 1000
14. VPVM - S 1200
15. VPVM - S 1500
16. VPVM - S 2000
17. VPVM - R 800
18. VPVM - R 1000
19. VPVM - R 1200
20. VPVM - R 1400
21. VPVM - R 1600
22. VPVM - R 2000

Example

Data input :
Outlet VPVM - K
V = 1400 m3.h-1
H = 1000 mm
∆tp = - 3 K
wL = 0,2 m.s-1

Preliminary design chart:
size 400

Diagram 1:
∆pc = 30 Pa
LWA = 23 dB(A)

Diagram 4:
L = 2,7 m
∆tL /∆tp (diagram) = 0,72

Correction to outlet height ∆tL /∆tp x 0,7 = 0,5

III. ORDERING DATA

OUTLET VPVM - K / 400 x 1000 / R - TPM 013 / 01

OUTLET
VPVM
-
K
/
400
x
1000
/
R
-
TPM 013 / 01
 
type
  K - round
S - wall-mounted
R - corner
 
size
height
 
with control flap
technical conditions

 

IV. MATERIAL

Outlet parts are made of steel sheet. The surface is finished with white baking varnish of RAL 9010 colour shade. Other shade requirements have to be agreed with the manufacturer in advance.

V. PACKING, TRANSPORT, ACCEPTANCE, STORAGE

Outlets are supplied in crates, covered with shrinkable foil, by covered transportation means. When handled during transport and storage, outlets must be protected against mechanical damage.

Provided no method of acceptance is determined in the order, outlets will be considered accepted when being handed over to the carrier.

Outlets must be stored in covered rooms, in environments free from aggressive vapours, gases and dust.

Temperature range of -5 to +40 °C and relative humidity up to 80% must be kept in the storage rooms.

The manufacturer provides outlets with an 18-month guarantee after having been first put into operation, however 24 months after the date of dispatching.

VI. RELATED STANDARDS, REGULATIONS AND PROTOCOLS

ČSN 12 0000 . . . . . . . . . . . . . . . .Air-conditioning equipment. Terminology.
ČSN 33 2000-5-54 . . . . . . . . . . .Grounding and electrical conductors.
ČSN EN 60 721-3-3 . . . . . . . . . . Classification of environmental conditions.
ČSN EN 1127-1 . . . . . . . . . . . . . .Explosive equipment. Prevention and protection against explosion. Part 1- Basic terms and methodology.
ČSN 33 2030 . . . . . . . . . . . . . . . .Protection against dangerous effects of static electricity.
ČÚBP Reg. No.48/82 Coll. . . . . .Basic requirements of safety at work and of technical equipment.
ČÚBP Reg. No.324/90 Coll. . . . .Safety at work and of technical equipment at building works.