VPVM - Large Area Outlet
Dimensions in mm, weights in kg.
These technical conditions define a series of the manufactured sizes and versions of the following large outlets (hereinafter outlets): VPVM - K 400, 600, 800, 1000, 1200, 1480, VPVM - S 400, 600, 800, 1000, 1200, 1500, 2000, VPVM - R 800, 1000, 1200, 1400, 1600, 2000 , heights of 750, 1000, 1250, 1500 and 2000 mm.
They apply to manufacturing, designing, ordering, deliveries, installation and operation.
I. GENERAL
1. Description
Large outlets are terminal air-conditioning elements for the distribution of air in air-conditioned and ventilated rooms. They are intended for the inlet of treated outdoor air directly into the living (working) area. In order to ensure stabilized air flow in the living area, the temperature of inlet air must be lower by 1 to 3°C then the temperature of air in the ventilated room. Outdoor air is let in with low velocity at the floor, to take harmful substances from the living area to ceiling.
2. Design
The following types of outlets are supplied: round outlets to be installed into a space, wall-mounted outlets with semi-circled ground plan, and corner outlets with quarter-circled ground plan. Piping is connected to outlets from above to round connecting socket. Outlets are supplied with or without control flaps.
Outlets are intended for installation in environments protected from weather conditions, class 3K5, according to ČSN EN 60 721-3-3 and in BNV rooms according to ČSN EN 1127-1.
3. Dimensions
Round outlet VPVM - K |
Size |
400 |
600 |
800 |
1000 |
1200 |
1480 |
øA |
400 |
600 |
800 |
1000 |
1200 |
1480 |
øD |
313 |
498 |
558 |
628 |
708 |
798 |
Height H: 750, 1000, 1250, 1500, 2000 |
 |
Wall-mounted outlet VPVM - S |
Size |
400 |
600 |
800 |
1000 |
1200 |
1500 |
2000 |
A |
400 |
600 |
800 |
1000 |
1200 |
1500 |
2000 |
B |
330 |
490 |
550 |
620 |
700 |
850 |
1100 |
C |
155 |
235 |
265 |
290 |
320 |
370 |
480 |
øD |
248 |
398 |
448 |
498 |
558 |
628 |
798 |
Height H: 750, 1000, 1250, 1500, 2000 |
 |
Corner outlet VPVM - R |
Size |
800 |
1000 |
1200 |
1400 |
1600 |
2000 |
A |
400 |
500 |
600 |
700 |
800 |
1000 |
C |
170 |
210 |
250 |
290 |
330 |
390 |
øD |
248 |
313 |
398 |
448 |
448 |
498 |
Height H: 750, 1000, 1250, 1500, 2000 |
 |
4. Weights
|
Size
|
Outlet height H [mm]
|
Regulation
|
750
|
1000
|
1250
|
1500
|
2000
|
VPVM − K
|
400 |
8,8 |
11,0 |
13,0 |
14,5 |
18,5 |
0,8 |
600 |
14,0 |
17,0 |
20,0 |
23,0 |
29,0 |
1,7 |
800 |
20,0 |
24,0 |
27,0 |
31,0 |
38,0 |
2,0 |
1000 |
27,0 |
31,0 |
35,5 |
40,0 |
48,5 |
2,5 |
1200 |
35,0 |
40,0 |
45,0 |
50,0 |
60,0 |
3,0 |
1480 |
46,5 |
53,0 |
59,0 |
65,0 |
77,0 |
3,7 |
VPVM − S
|
400 |
11,0 |
13,0 |
16,0 |
18,5 |
24,0 |
0,6 |
600 |
17,0 |
21,0 |
25,0 |
29,0 |
37,0 |
1,2 |
800 |
21,0 |
26,0 |
30,0 |
35,0 |
44,0 |
1,4 |
1000 |
25,5 |
31,0 |
36,0 |
41,5 |
52,0 |
1,6 |
1200 |
30,5 |
36,5 |
43,0 |
49,0 |
61,0 |
2,0 |
1500 |
37,0 |
47,0 |
54,5 |
62,0 |
76,5 |
2,5 |
2000 |
58,0 |
67,0 |
77,0 |
86,0 |
106,0 |
3,7 |
VPVM − R
|
800 |
12,0 |
15.0 |
17,5 |
20,5 |
26,5 |
0,6 |
1000 |
15,0 |
19,0 |
22,5 |
26,0 |
33,5 |
0,8 |
1200 |
19,0 |
23,5 |
28,0 |
32,0 |
41,0 |
1,2 |
1400 |
23,0 |
28,0 |
33,0 |
38,0 |
48,5 |
1,4 |
1600 |
26,5 |
32,0 |
38,0 |
43,5 |
55,0 |
1,4 |
2000 |
35,0 |
42,0 |
49,0 |
56,0 |
70,0 |
1,7 |
Note: The weights provided apply to outlets without control equipment. For versions including control equipment, the weight of the control equipment has to be added.
5. Location, Installation
Round outlets VPVM - K are intended for installation in free space, to be anchored to the floor. Wall-mounted outlets VPVM - S and corner outlets VPVM - R are installed onto walls and in corners, to be anchored either to the floor or to the wall (in the corner).
Floor-mounting example |
VPVM - K
|
VPVM - S
|
VPVM - R |
 |
 |
 |
Anchoring example - detail X |
|
Legend:
1. VPVM
2. anchoring plate
3. metal sheet screw ø 4,2 mm
4. countersunk screw ø 6 mm
5. dowel |
Large outlet supply includes 6 anchoring plates (Pos. 2) and 6 metal-sheet screws, ø 4,2 mm (Pos. 3).
Connecting material (Pos. 4 and 5) is not included in the supply.
II. TECHNICAL DATA
Preliminary outlet design |
Vmax [m3.h−1]
|
Size
|
socket øD [mm]
|
Outlet height H [mm]
|
750
|
1000
|
1250
|
1500
|
2000
|
VPVM − K
|
400 |
313 |
1250 |
1400 |
1500 |
1650 |
1800 |
600 |
498 |
2400 |
2600 |
2900 |
3100 |
3300 |
800 |
558 |
3100 |
3450 |
3600 |
3900 |
4200 |
1000 |
628 |
3800 |
4230 |
4500 |
4800 |
5300 |
1200 |
708 |
4700 |
5300 |
5500 |
6000 |
6500 |
1480 |
798 |
6100 |
6660 |
7000 |
7660 |
8100 |
VPVM − S
|
400 |
248 |
660 |
730 |
770 |
830 |
900 |
600 |
398 |
1400 |
1530 |
1700 |
1800 |
1900 |
800 |
448 |
1800 |
2000 |
2100 |
2250 |
2450 |
1000 |
498 |
2200 |
2430 |
2600 |
2800 |
3000 |
1200 |
558 |
2750 |
3050 |
3200 |
3450 |
3700 |
1500 |
628 |
3450 |
3800 |
4000 |
4300 |
4600 |
2000 |
798 |
5150 |
5800 |
6000 |
6500 |
7000 |
VPVM − R
|
800 |
248 |
660 |
730 |
770 |
830 |
900 |
1000 |
313 |
1150 |
1200 |
1400 |
1500 |
1600 |
1200 |
398 |
1400 |
1530 |
1700 |
1750 |
1900 |
1400 |
448 |
1600 |
1750 |
1800 |
2000 |
2150 |
1600 |
448 |
1800 |
2000 |
2100 |
2250 |
2450 |
2000 |
498 |
2200 |
2430 |
2600 |
2800 |
3000 |
Effective area Sef [m2]
|
VPVM − K
|
π . D . H . K |
K = 0,63 |
VPVM − S
|
0,5. π . A . H . K |
VPVM − R
|
0,5. π . A . H . K |
6. Calculation and Determination Quantities
|
V [m3.h-1] - volumetric flow rate for one outlet
∆pc [Pa] - total pressure loss at ρ = 1,2 kg.m-3
LWA [dB(A)] - acoustic power level
wL [m.s-1] - flow velocity in L distance from outlet
∆tP [K] - difference between inlet air temperature and room air temperature
∆tL [K] - difference between room air temperature and flow air temperature in L distance |
Pressure Losses and Acoustic Powers
Correction to outlet height (applicable to Diagrams 1 to 3) |
|
Outlet height H
|
750
|
1000
|
1250
|
1500
|
2000
|
Δpc
|
x 1,1 |
x 1 |
x 0,9 |
x 0,8 |
x 0,7 |
LWA
|
+ 1 |
0 |
− 1 |
− 1 |
− 2 |
1. VPVM - K |
 |
2. VPVM - S |
 |
3. VPVM - R |
 |
Flow Velocity and Temperature Coefficient
Correction to outlet height (applicable to Diagrams 4 to 22) |
| |
Outlet height H [ mm ]
|
750
|
1000
|
1250
|
1500
|
2000
|
wL [m.s-1]
|
x 0,95 |
x 1 |
x 1,05 |
x 1,1 |
x 1,15 |
∆tL / ∆tP
|
x 0,65 |
x 0,7 |
x 0,75 |
x 0,8 |
x 0,9 |
4. VPVM - K 400 |
 |
5. VPVM - K 600 |
 |
6. VPVM - K 800 |
 |
7. VPVM - K 1000 |
 |
8. VPVM - K 1200 |
 |
9. VPVM - K 1480 |
 |
10. VPVM - S 400 |
 |
11. VPVM - S 600 |
 |
12. VPVM - S 800 |
 |
13. VPVM - S 1000 |
 |
14. VPVM - S 1200 |
 |
15. VPVM - S 1500 |
 |
16. VPVM - S 2000 |
 |
17. VPVM - R 800 |
 |
18. VPVM - R 1000 |
 |
19. VPVM - R 1200 |
 |
20. VPVM - R 1400 |
 |
21. VPVM - R 1600 |
 |
22. VPVM - R 2000 |
 |
Example
Data input
:
Outlet VPVM - K
V = 1400 m3.h-1
H = 1000 mm
∆tp = - 3 K
wL = 0,2 m.s-1
Preliminary design chart:
size 400
Diagram 1:
∆pc = 30 Pa
LWA = 23 dB(A)
Diagram 4:
L = 2,7 m
∆tL /∆tp (diagram) = 0,72
Correction to outlet height ∆tL /∆tp x 0,7 = 0,5
III. ORDERING DATA
OUTLET VPVM - K / 400 x 1000 / R - TPM 013 / 01
OUTLET
|
VPVM
|
-
|
K
|
/
|
400
|
x
|
1000
|
/
|
R
|
-
|
TPM 013 / 01
|
| |
type |
|
K - round
S - wall-mounted
R - corner |
|
size |
|
height |
|
with control flap |
|
technical conditions |
IV. MATERIAL
Outlet parts are made of steel sheet. The surface is finished with white baking varnish of RAL 9010 colour shade. Other shade requirements have to be agreed with the manufacturer in advance.
V. PACKING, TRANSPORT, ACCEPTANCE, STORAGE
Outlets are supplied in crates, covered with shrinkable foil, by covered transportation means. When handled during transport and storage, outlets must be protected against mechanical damage.
Provided no method of acceptance is determined in the order, outlets will be considered accepted when being handed over to the carrier.
Outlets must be stored in covered rooms, in environments free from aggressive vapours, gases and dust.
Temperature range of -5 to +40 °C and relative humidity up to 80% must be kept in the storage rooms.
The manufacturer provides outlets with an 18-month guarantee after having been first put into operation, however 24 months after the date of dispatching.
VI. RELATED STANDARDS, REGULATIONS AND PROTOCOLS
ČSN 12 0000 . . . . . . . . . . . . . . . .Air-conditioning equipment. Terminology.
ČSN 33 2000-5-54 . . . . . . . . . . .Grounding and electrical conductors.
ČSN EN 60 721-3-3 . . . . . . . . . . Classification of environmental conditions.
ČSN EN 1127-1 . . . . . . . . . . . . . .Explosive equipment. Prevention and protection against explosion.
Part 1- Basic terms and methodology.
ČSN 33 2030 . . . . . . . . . . . . . . . .Protection against dangerous effects of static electricity.
ČÚBP Reg. No.48/82 Coll. . . . . .Basic requirements of safety at work and of technical equipment.
ČÚBP Reg. No.324/90 Coll. . . . .Safety at work and of technical equipment at building works.